15 KVA / 12 KW Kirloskar Diesel Generator on Rent  

15 KVA / 12 KW Kirloskar Diesel Generator on Rent

GENSET DETAILS

Prime Rating at rated rpm
15 KVA / 12 KW
Genset Model
KG1-15AS
Frequency
50 Hz
Power factor
0.8 lagging
Voltage
230 (1Ø ) & 415 (3Ø) V
Governing class
G2
Noise level
dBA < 75
Fuel Consumption
Load 100%
4 Ltrs/Hr
Load 75%
3 Ltrs/Hr
Load 50%
2.2 Ltrs/Hr
Fuel Tank Capacity
65 Ltrs
Dimensions (L x W x H)
1740 x 1050 x 1410 mm
Dry weight with Canopy
900 Kg
Wet weight with Canopy
950 Kg
Electrical Battery
12 Volts-DC

ENGINE DETAILS

Engine Model
HA294 G1
Rated output
15.1 kW
Rated output
20.5 HP
No. of cylinder
2
Cubic capacity
1.88 Ltrs
Bore x Stroke
100 x 120 mm
Rated Speed
1500 RPM
Aspiration
NA NA/TC/TA
Lube Oil change period
500 hrs.
Lube oil Sump Capacity
5 Ltrs
Coolant Capacity
NA Ltrs

ALTERNATOR DETAILS

Insulation Class
Class H
Alternator Efficiency
86 %
Max Voltage Dip at Full Load 0.8 pf Lag
< 20 % sec
Max Time to build up rated voltage at Rated RPM
< 5 sec provided engine reach the rated speed

PRIME RATTING AND STANDARD BY RATING

'Prime power' is designed for Unlimited hours, as compared to 'Emergency stand-by' designed for 200 hours in a year. Prime rated Gensets also permit 10% temporary overloading. Users need to carefully select the Genset rating to meet their requirement. KOEL offers Prime power as standard offer. Contact KOEL for stand-by ratings.

ENGINE CAPACITY DOES MATTER

Engine capacity (cc) plays a vital role in Genset performance. Higher engine capacity leads to a robust and stable Genset performance. Higher engine capacity also enables Genset to respond quickly & positively to sudden load additions.
Canopy features
  • Ease of Access and Serviceability
  • Aesthetically designed, weather and sound resistant enclosure
  • Insulation conforms to UL94-HF1 class for flammability
Controller features
  • Microprocessor based fully configured
  • Graphical bigger LCD display
  • Best in class monitoring and diagnostic
  • Integrable with AMF, synchronization & communication configurations
Engine features
  • O2E Series: Low emission, high efficiency engines
  • Compact, Robust and Rugged Design
  • 500 hours lube-oil change period
Alternator features
  • Best In Class Efficiency
  • Special Windings to Reduce Harmonics
  • Vacuum Pressure Impregnation and epoxy gel coating on winding
Monitoring features
  • Phase Voltages, Phase Currents, kVA, KW, KVAr, KWH, Power Factor
  • Lube oil Pressure, Engine Temperature, RPM, Run Hours, Number of starts, Fuel Level, Auto / Manual Stop
  • Battery charge condition
  • Common Alarm / Hooter output, AMF feature with ATS
Optional features
  • Modbus communication
Optional features

Diagnostic Features

KG934 Controller

KG934 Controller

  • Battery charging failure, Over/Under speed, Over Current, Over/Under Voltage, Over KW, Phase Sequencing, Phase missing
  • Low Lube oil Pressure, High Engine Temperature, Low/High battery voltage, Low Fuel Level, Over Crank protection, Routine Maintenance indicator, Genset Test Facility

Being in control of your Genset is certainly a winning edge!